ICM ICM220 Lockout Protection Module, 18-30 VAC

Availability:
In-Stock

Mode of Operation - Upon application of power with the safety switches closed, the load will energize. If any of the safety switches open for longer than 600 ms, the fault light will come on and the load will stay de-energized regardless of the state of the safety switches. Power must then be removed for 100 ms and safety switches must be closed in order to re-energize the load, upon which the fault light will be off.

ICM offers low cost lockout protection modules that monitor various switch inputs to help protect your compressor.

Features

  • UL 873 recognition as compressor controller
  • Low cost lockout relay
  • Helps eliminate nuisance lockouts typical of Series 84 and 93 impedance relays
  • Ideal for use with safety/interlock switches
  • Replaces impedance relays Series 84 and 93

$33.03 USD

Title
Buy Now
SKU:
ICM220
ID:
PH501-2S9-3215

SPECIFICATIONS

General Information    

Product Type
Lockout Protection Module
Frequency
50-60 Hz
Relays
1 form C
Size
2" x 2"
Voltage
18/30 VAC
Power Consumption
2 Watts Max @ Lockout
Contacts
2 amps @ 30 VAC resistive